3701-31-04 (B)(1)(b) / SVRS device(s) shall be functional.
Critical The SVRS device that is being used as a secondary means to prevent entrapment/evisceration was not functional at the time of the inspection. Observed the screen of the decive reading "SET-UP REQUIRED, REFER TO MANUAL".
Do not operate the pool when the SVRS is not functioning. Ensure the SVRS is operating properly prior to placing the pool back into operation.Discussed with PIC.
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records. Oberved that pool records did not all have dates. Last dated record week was week ending 5 OCT.
All facility records must be maintained and available for review upon request. Please ensure the records are properly dated.
3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Disinfection residuals were not tested daily at pool side and/or at the required intervals for pools/automatic chemical controllers/special features. Observed that the pool is not being tested prior to opening every day, record was not recorded yet and inspection was in the afternoon.
Pleast insure to test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. If an ACC is in use the disinfectant residual must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the disinfectant residual must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(6)(j) / All SVRS devices are maintained/ functional and tested
Critical SVRS devices were not maintained or not functional.
Restore all SVRS devices to proper working order to prevent entrapment or evisceration.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 16-October-2019
Comments |
---|
Consulted with the PIC on the spineboard. The surface has been sanded very well but can still splinter and is not smooth. Discussed adding some sort of substance to make smooth. Reinspection for 17 OCT 2019. |