3701-31-04 (B)(6)(a) / Pool structure is water tight
Observed paint chipping off bottom of pool.
In order to maintain that the pool is cleanable and water tight, ensure bottom of pool is in good repair.
3701-31-04(D)(6)(a)(1) / Combined chlorine shall not exceed 1.0 ppm.
Combined chlorine was greater than 1.0 ppm. Observed combined chlorine to be at 2 ppm.
In order to reduce the risk of health hazards, treat the pool so that the combined chlorine is less than 1 ppm.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Pool free chlorine disinfectant residual was below 1 ppm. Observed free chlorine disinfectant residual at 0.5 ppm.
In order to reduce the risk of health hazards, do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Raise free chlorine disinfectant residual to at least 1 ppm.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 30-December-2021
Comments |
---|
Pool is closed due to not having pool chemical. Facility will contact CCCHD when pool chemicals come in and pool chemicals are corrected. |