3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. Observed a pH of 7.0.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04(D)(6)(a)(1) / Combined chlorine shall not exceed 1.0 ppm.
Combined chlorine was greater than 1.0 ppm. Observed combined chlorine to be 2.0 ppm.
Treat the pool so that the combined chlorine is less than 1 ppm.
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 08-August-2016