3701-31-04(D)(6)(a)(1) / Combined chlorine shall not exceed 1.0 ppm.
Combined chlorine was greater than 1.0 ppm. Observed combined chlorine to be 1.5 ppm.
Treat the pool so that the combined chlorine is less than 1 ppm. Combined chlorine must be less than or equal to 1 ppm. Adjust the level to make it within acceptable range.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat Pool free chlorine disinfectant residual was below 1 ppm. Observed free chlorine disinfectant residual to be 0.5 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Adjust the levels of the disinfectant residual to be within acceptable range.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 03-August-2015