3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Observed ORP value of 629 mv.
ORP reading was below 650 mv. Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Observed the flow meter not working properly.
Required meters and gauges were not maintained or were not functional while the pool is in operation. Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation.
3701-31-04 (D)(7)(c) / Audible/visual alarm shall activate when unit is malfunctioning or when pH or ORP levels are not acceptable.
Critical Observed the ACC in alarm.
The ACC unit was not activating an audible or visual alarm when unit malfunctioned or when pH or ORP levels were not acceptable. Have the ACC unit serviced or replaced so that the audible or visual alarm is activated when necessary.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 24-October-2018