3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Observed flow (58gpm) to be to high for filter (44gpm max)
In order to reduce the risk of safety hazards, ensure flow is adjusted.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Observed pH(7.0) was outside the range of 7.2 to 7.8.
In order to reduce the risk of safety hazards, treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity (40ppm) was less than 60 ppm.
In order to reduce the risk of safety hazards, raise the total alkalinity to at least 60 ppm.
3701-31-04 (E)(2)(d) / First aid kit provided
Observed first aid kit was starting to look sparse.
In order to reduce the risk of safety hazards, ensure first aid kit has gloves and sufficient supply of materials to stop bleeding.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 22-January-2021