3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. 3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8. pH was over 8.0.
Treat the pool water so that the pH is within the acceptable range. 3701-31-04 (C)(7) / Spa water temperature is less than 104 degrees Fahrenheit/ thermometer is provided
Repeat Corrected During Inspection Spa water temperature was greater than 104 degrees Fahrenheit.
Do not operate the spa at a water temperature greater than 104 degrees Fahrenheit. Reduce the water temperature to 104 degrees or less. 3701-31-04 (D)(8)(a) / DPD test kit used for testing water quality.
DPD test kit was not used for testing water quality.
Obtain a DPD test kit to test water quality of the pool. Please provide a new DPD kit.
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 21-October-2014