[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Observed turnover rate to only be ~35 gpm, due to the filter only being able to hand 40 gpm.
The required circulation rate for this spa is 105 gpm. Please have the circulation system assessed to see if other factors are leading to the insufficient flow. In the meantime, please record the water chemistry every 2 hours, including chlorine, free chlorine, combined chlorine, and pH, and maintain these records. These records must be maintained for review during future inspections.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Observed pH to be more than 8.0.
pH must be within the range of 7.2 to 7.8. Treat the pool water so that the pH is within the acceptable range.


Inspection Information


Facility Type: Spa

[?] Inspection Type: Follow-up

Inspection Date: 04-April-2014

The following violation(s) have been corrected since the last inspection.
Comments
Testing frequency fact sheet will be provided.