[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. A noticeable leak is present in the chlorine storage tank and chlorine has pooled on the floor of the pump room and around several pieces of equipment. Chlorine is very corrosive and can damamge equipment. Mke arrangements IMMEDIATELY to drain the tank and rinse the pump room floor to remove chlorine residues.
All equipment must be maintained in accordance with the manufacturers specifications.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Perimeter gate does not self-close and self-latch.
Repair the perimeter gate so that it self-closes and self-latches to prevent unauthorized access.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 26-September-2014

Comments
Please treat for combined chlorine.

Please make arrangements for additional training from Ecolab to ensure that Marvin and Jeff are fully knowledgeable about how the system works and how to do any needed adjustments.