3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Observed free chlorine to be too low (0ppm)
In order to reduce the risk of health hazards, ensure free chlorine is at 1 or above.
3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Observed that the disinfection residuals were not tested daily at pool side and/or at the required intervals for pools. (missing last 3 days)
Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use.
3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Observed that pH was not tested and recorded daily at pool side. (missing last 3 days)
In order to reduce the risk of safety hazards, ensure that the pH is tested prior to bathers entering the water and every 4 hours the pool is open for use.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat Observed pH to be too low (7.0).
In order to reduce the risk of health hazards, ensure to treat the pool water so that the pH is within the acceptable range (7.2-7.8).
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Observed the total alkalinity (50ppm) was less than 60 ppm.
In order to reduce the risk of health hazards, ensure to raise the total alkalinity to at least 60 ppm.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 26-February-2021