3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Observed that the pool was not tested before bathers entered into the water on 2/8/22.
In order to reduce the risk of health hazards, ensure that the disinfection residuals are tested daily at pool side and/or at the required intervals for pools/automatic chemical controllers/special features. Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. If an ACC is in use the disinfectant residual must be tested every 12 hours while the pool is in use.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Observed that the pool free chlorine disinfectant residual to be 0 ppm
In order to reduce the risk of health hazards, ensure that the free chlorine disinfectant residual is above 1ppm. PIC started the chlorine feeder during the inspection and will reinspect before the next session. Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Correct By: 09-Feb-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 08-February-2022
Comments |
---|
PIC to check the chlorine levels in a few hours, before the next session to verify that the chlorine has increased since the feeder was turned on. |