3701-31-04(D)(6)(a)(1) / Combined chlorine shall not exceed 1.0 ppm.
Tested combined chlorine to be 1.5 ppm during inspection. The combined chlorine is not to exceed 1.0 ppm to ensure the chlorine in the water is available to work as an effective disinfectant treatment of the pool water. Adjust to lower the combined chlorine level to be 1.0 ppm or less.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 31-May-2022
Comments |
---|
The pool was closed during inspection after redoing the pool floor and the operator adjusting the water chemistry. Tiled surface of the pool was removed and the pool refilled. Current the pool has to be refilled daily due to a lost of water. Free chlorine levels tested at high concentration of 17 when required to have a min. of at least 1.0 ppm. It is not a violation to have the free chlorine greater than 1.0 ppm but greater concentrations could result in skin irritations and bleaching of swim wear of patrons using the pool. Pool operator is working on this issue |