3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Observed several tiles inside the pool are missing.
The pool shall be maintained in good repair. All equipment must be maintained in accordance with the manufacturers specifications. Replace the missing tiles.
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Observed no backflow prevention device on the hose bibb in the pool room and on the pool fill line in the pump room.
Cross connection hazards shall be prevented. Supply proper backflow prevention devices at these 2 locations.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Observed a pH reading of 7.0.
The range for pH shall be between 7.2 to 7.8. Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Observed that the cyanuric acid level was greater than 100 ppm.
Cyanuric acid level shall not exceed 70 ppm. Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly. Take measures to adjuct the cyanuric acid levels to or below 70 ppm.
3701-31-04 (D)(8)(a) / DPD test kit used for testing water quality.
Observed that the operator is using a standard DPD test kit, and the free chlorine is above 5 ppm.
The test kit should measure the free, combined and total chlorine. Obtain a DPD test kit to test water quality of the pool. Either maintain total chorine at less than 5 ppm at all times, or provide a FAS-DPD test kit capable of measuring higher chlorine levels.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 07-March-2018
Comments |
---|
Met with PIC of pool, Dee, and demonstrated to him how to properly test the pool for free, combined and total chlorine using the FAS-DPD test kit. Also tested for cyanuric acid and explained to him why this level was so high and walked him through what he needs to do in order to lower this level. Also tested for pH, and it was too low, so we explained to him how to increase the pH using soda ash (sodium carbonate). |