3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Observed that records of water testing had only been kept until 10/10/2023. In order to ensure proper chemical composition of the facility’s pool over time, chemical pool records must be maintained regularly.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Observed total alkalinity at 40ppm. In order to reduce the risk of major pH fluctuations, ensure that alkalinity is at 60ppm or above. Discussed with person in charge.
3701-31-04 (D)(7)(b) / pH and ORP values shall be displayed.
Critical Repeat Observed ORP value was not displayed on the ACC unit. Discussed with person in charge. Ecolab is waiting on the part to become available to correct the issue. Have the ACC unit serviced or replaced so that the ORP value is displayed when the parts are available.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 16-October-2023