3701-31-04 (B)(6)(u) / Ventilation system is maintained/ free of hazards
Observed that the ventialation system is the pool room was not working properly with little to no air flow.
In order to reduce the risk of health hazards, ensure that the pool room ventilation system is repaired/replaced. PIC stated they have obtained a couple of estimates at this point. CCCHD will continue to track the progress of this repair.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 17-October-2023
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (C)(2)/pH is within 7.2 to 7.8 Observed the pH was 7.0. In order to reduce the risk of potential health hazards, ensure that the pH is between 7.2 and 7.8. Treat the pool water so that the pH is within the acceptable range. |
3701-31-04(D)(6)(a)(2)/Pool free chlorine disinfectant residual shall be above 1 ppm. Observed pool free chlorine disinfectant residual was below 1 ppm (0 ppm). In order to reduce risk of health hazards, ensure that the pool is treated to maintain 1 ppm. Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. PIC closed the pool. |