3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Observed that disinfection residuals were not tested daily at pool side and/or at the required intervals for pools/automatic chemical controllers.
In order to reduce the risk of health hazards, ensure to test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. If an ACC is in use the disinfectant residual must be tested every 12 hours while the pool is in use. Test and record disinfection residuals at required frequency.
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Observed that combined chlorine was not tested/recorded daily at pool side prior to use.
In order to reduce the risk of health hazards, test for combined chlorine prior to bathers entering the water and If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. Test and record combined chlorine at required frequency.
3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Observed that pH is not being tested at required frequency.
In order to reduce the risk of health hazards, pH must be tested prior to bathers entering the water and as long as ACC is working properly, every 12 hours while the pool is in use. Test and record pH at required frequency.
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Observed that water temperatures were not being tested and recorded daily.
In order to reduce the risk of health hazards, take and record the water temperature at least once a day. Test and record water temperature at required frequency.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Observed that the flow meter appears to be stuck and not functioning properly.
In order to maintain proper flow rate, ensure flow meter is working properly.
3701-31-04(D)(6)(a)(1) / Combined chlorine shall not exceed 1.0 ppm.
Observed that combined chlorine is at 1.5ppm.
In order to reduce the risk of health hazards, treat the pool so that the combined chlorine is less than 1 ppm.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 25-June-2021
Comments |
---|
Combined chlorine is still out. |