[?] A summary of the violations found during the inspection are listed below.

No critical violations were documented at the time of inspection.

No violations were documented at the time of inspection.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Follow-up

Inspection Date: 08-October-2021

The following violation(s) have been corrected since the last inspection.
3701-31-04 (B)(1)(e)/Automatic Chemical Controller (ACC) shall function properly.
Observed that the Automatic Chemical Controller (ACC) was in alalrm at the time of the inspection
In order to reduce the risk of safety hazards, do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
3701-31-04(D)(6)(a)(1)/Combined chlorine shall not exceed 1.0 ppm.
Observed that combined chlorine was 1.5 ppm.
In order to reduce the risk of health hazards, treat the pool so that the combined chlorine is less than 1 ppm.
3701-31-04(D)(6)(a)(2)/Pool free chlorine disinfectant residual shall be above 1 ppm.
Observed free chlorine disinfectant residual was 0.5 ppm.
In order to reduce the risk of health hazards, treat the pool until the chlorine disinfectant residual is at 1 ppm or above.