3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Observed that the testing records for the spa do not reflect that the spa is being tested with the required frequency.
All facility records must be maintained and available for review upon request. The bromine must be checked before the spa is used and at least every 12 hrs thereafter. The pH must be checked befoer the spa is used and at least every 4 hours thereafter. The water temperature shall be checked dialy. The alkalinity shall be checked once per week. Please revise testing requirements and record keeping to reflect this schedule.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Flow meter is not functioning.
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation. Repair/replace the flow meter so that you can determine the flow rate of the spa.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The permiter gate does not self close.
Repair/replace the gate so that it self closes and latches.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Observed the pH to be 8.0.
The pH shall be maintained between 7.2 and 7.8 at all times. Adjust the pH to comply with rule.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was observed at 40 ppm.
Total alkalinity shall be over 60 ppm.
3701-31-04 (C)(7) / Spa water temperature is less than 104 degrees Fahrenheit/ thermometer is provided
Water temperature observed at 106 degF.
Spa water shall be maintained at 104 degF of less at all times. Reduce the water temperature.
Facility Type: Spa
[?] Inspection Type: Follow-up
Inspection Date: 10-February-2016
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(6)(v)/Electrical components are maintained/ free of hazards Observed that the switch cover was missing for the blower motor controls. Electrical components shall be maintained in a safe fashion. Replace the cover for the switch. |
Comments |
---|
The switch cover for the blower motor control has been replaced. This corrects the only critical violation that remained from the previous standard inspection. Please be sure to follow up on non-critical violations before the next standard inspection. |