3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
The deck surface around the pool had several areas where the surface finish was chipped, cracked, or had worn paint.
Repair areas of the deck where the surface is broken, cracked, chipped, or has worn paint. If more than 50% of the deck must be replaced, plans must be submitted to the Ohio Department of Health for review and approval.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 11-April-2014
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(1)(e)/Automatic Chemical Controller (ACC) is functioning properly Observed the pool Automatic Chemical Controller (ACC) to not function properly at the time of the inspection - the warning lights were flashing and the chlorine level - while sufficient for adequate disinfection - did not appear to be uniform at the set levels. The pool may remain open, but the unit must be professionally checked and repaired or adjusted. Ensure that the ACC unit is functioning properly prior to the scheduled follow-up inspection on April 4, 2014 at 3:30pm. |
3701-31-04 (B)(6)(h)/Required meters and gauges maintained/functional The flowmeter was "stuck" in the tube and did not allow the check of the flow speed. Required meters and gauges were not maintained or were not functional while the pool is in operation. Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation. Repair or replace this gauge to ensure easy and frequent checks of the flow speed. |
3701-31-04 (C)(2)/pH is within 7.2 to 7.8 The pH level was measured at less than 7.0- outside the range of 7.2 to 7.8. Treat the pool water so that the pH is within the acceptable range. Correct By: 11-Apr-2014 |