3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat The hose attached to the pool fill system is not protected from backflow.
The potable water system shall be protected from potential contamination. Install an approved backflow prevention device on the pool fill hose.
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps shall have an air gap and remain open to freely drain.
Repeat Observed that there is not an air gap between the DE filter drainage lines and the waste sump.
Raise the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity observed at 30 ppm.
Total alkalinity shall be at least 60 ppm. Raise the total alkalinity to at least 60 ppm.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 20-August-2015