3701-31-04 (D)(7)(a) / pH and ORP values for chlorine/bromine shall be continuously monitored.
Critical Repeat Corrected During Inspection Observed that the ACC was off at the time of inspection.
In order to reduce the risk of health hazards, the pH and ORP values shall be continuously monitored. Have the ACC unit serviced/repaired/replaced so that the pH values are continuously monitored. While ACC is not working properly, check the pool before bathers enter and then every 4 hours while the pool is open. Discussed this with the PIC and he will monitor every 4 hours until the ACC is repaired/replaced.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 17-December-2019