3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm. Observed total alkalinity at 50 ppm.
Raise the total alkalinity to at least 60 ppm.
3701-31-04 (C)(7) / Spa water temperature is less than 104 degrees Fahrenheit/ thermometer is provided
Repeat Corrected During Inspection Observed the spa water temperature at 106 degrees F.
Owner adjusted the water temperature and 104 degrees F was reached during inspection.
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 18-October-2016
Comments |
---|
Discussed with owner about using baking soda (sodium bicarbonate) to raise the total alkalinity. |