3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Observed a leak under the chemical feeder that appeared to come from a leaking valve. In order to ensure the proper disinfectant residual, it is necessary that the chemical feeder be intact and in good working condition. Check and repair the feeder.
All equipment must be maintained in accordance with the manufacturers specifications.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Pool free chlorine disinfectant residual was below 1 ppm. The chlorine disinfectant residual was measured at 0 ppm. In order to reduce the risk of pathogen growth in the pool water and the risk of disease, it is necessary that the disinfectant residual be maintained at or above 1ppm. Discussed with the PIC, who indicated that he thought the valve on the chemical feeder was broken and that a repairman was scheduled to come to the facility this evening to check the system and try to restore the proper chlorine residual. Always maintain the proper disinfectant residual. The pool was closed during the inspection.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 21-June-2021
Comments |
---|
The chlorine level was measured at 0 ppm. The person in charge indicated that a valve on the Pentair chemical feeder appeared to be broken, there was a leak at the valve, and the chlorine level in the pool could not be brought to the proper level. He indicated that a repair person was scheduled to come to the facility later in the evening to check the system and, if possible, make a repair. He also indicated that a staff meeting had been scheduled for 9:00 am on 06-22-2021 to discuss the issue. THE POOL WAS CLOSED DURING THE INSPECTION AND WILL BE KEPT CLOSED UNTIL THE DISINFECTANT RESIDUAL CAN BE RESTORED TO REQUIRED LEVELS. The Health District will return in the morning to check any repairs made on 06-21-2021 and, if possible, re-open the pool. |