3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Repeat Disinfection residuals were not tested daily (Saturdays and Sundays) at pool side and/or at the required intervals for pools/automatic chemical controllers/special features.
In order to reduce the risk of health hazards, test the disinfection residual every day before bathers the water. Disinfection residual must be tested every 4 hours when an ACC is not in use. If an ACC is in use the disinfectant residual must be tested every 12 hours while the pool is in use.
3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Repeat Corrected During Inspection Observed the pH was not tested (Saturday and/ or Sunday) daily at pool side and/or at required intervals for pools/automatic chemical controllers/special features.
In order to reduce the risk of health hazards, ensure that pH is tested prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use pH must be tested every 12 hours while the pool is in use.
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Repeat Observed water temperatures were not being recorded daily (Saturday and/ or Sunday).
In order to reduce the risk of health hazards, take and record the water temperature at least once/day.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Observed required turnover rates were not met, flow is approximately at 30gpm.
In order to reduce the risk of health hazards, ensure that turnover rates are being met. Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 28-October-2021
Comments |
---|
Pool chemical log is not being filled out regularly on Saturdays and Sundays. The flow has not changed and is still low. |