No critical violations were documented at the time of inspection.
No violations were documented at the time of inspection.
Facility Type: Commercial FSO < 25000 sq. ft.
[?] Inspection Type: Other
Inspection Date: 26-November-2014
Comments |
---|
This facility has submitted a facility review and have requested a final approval of the changes that were completed. An additional hand washing sink, food preparation sink with proper backflow prevent, and a service sink has been provided. All sinks were installed under proper permits. See final building inspection report in file. Only the plumbing was altered during this review. All Lighting and site plans did not change and will remain in the existing state. During the final inspection the following was observed and must be completed: 1) Provide a proper air gaps on the drainage pipes from the Ice machine and walk-in cooler drainage. 2) Caulk or provide a coved base molding along the base of the grease trap. 3) Current primary hot water generator is a 40,000 BTU tank. FDA guidelines requires this facility to be provided with a primary hot water generator of at least 80,000 BTU. The current tank is acceptable until it is not longer in proper working order. At that time the Hot water generator shall be replaced with a generator that meets this requirement. These items will be re-checked at the next standard inspection. Facility Review has been completed. |