3717-1-07.1(A) / Storage: separation.
Critical CorrectedDuringInsp Observed improper storage of poisonous or toxic materials. Fly spray was stored in the kitchen.
Poisonous or toxic materials shall be stored so they cannot contaminate food, equipment, utensils, linens, or single-service or single-use articles . To prevent accidental poisoning,
STORE THE FLY SPRAY IN THE MOP ROOM. Correct By: 25-Jan-2014
3717-1-04.4(M) / Mechanical warewashing equipment - sanitization pressure.
The water flow pressure in a warewashing machine is not adequate. Rinse pressure is 8 PSI.
The flow pressure of the fresh hot water sanitizing rinse in a warewashing machine, as measured in the water line immediately downstream or upstream from the fresh hot water sanitizing rinse control valve, shall be within the range specified on the machine's data plate and not be less than five pounds per square inch or more than thirty pounds per square inch.
ADJUST THE FINAL RINSE WATER PRESSURE TO BETWEEN 15 AND 25 PSI. MANUALLY SANITIZER THE DISHES IN THE SINK UNTIL FIXED. Correct By: 25-Feb-2014
3717-1-06.4(A) / Repairing.
The physical facilities are not being maintained in good repair. The light over the 3 compartment sink under the bar did not work.
The physical facilities shall be maintained in good repair.
REPAIR THE LIGHT UNDER THE BAR OVER THE 3 COMPARTMENT SINK. Correct By: 25-Feb-2014
Facility Type: Commercial FSO < 25000 sq. ft.
[?] Inspection Type: Standard
Inspection Date: 25-January-2014
Comments |
---|
Find the bar sanitizer test strips. The residential equipment must be replaced with commercial equipment (2 microwave ovens,refrigerator, freezer) |