[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 06-July-2023


Comments
ORP and pH were outside of required ranged, please adjust pool chemistry. KJS