3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Corrected During Inspection Pool free chlorine disinfectant residual was below 1 ppm. Correction: added chlorine to the pool.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records. Correction: reviewed proper records with PIC. Please keep accurate operation records.
All facility records must be maintained and available for review upon request.
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine was not tested daily at pool side prior to use. Reviewed how to properly measure combined chlorine with staff member.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(5) / Records are maintained for at least two years
Records were not maintained for at least two years.
Maintain all records and have them available upon request.
3701-31-04 (D)(8)(b) / FAS-DPD test kit used (when standard DPD test kit insufficient)
FAS-DPD test kit was not used when required.
Obtain a FAS-DPD test kit immediately.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 28-September-2023
Comments |
---|
Facility in good repair at the time of inspection. |