[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm. Alkalinity is 30 ppm.
Raise the total alkalinity to at least 60 ppm.


Inspection Information


Facility Type: Spa

[?] Inspection Type: Standard

Inspection Date: 29-February-2024


Comments
The facility is clean at the time of inspection. Alkalinity recorded at 30 ppm at the time of inspection.