[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Chlorine disinfectant residual was less than 1 ppm for the pool.
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Repeat Equipment/chemical/storage areas were not secured.
These storage areas must be kept inaccessible to everyone but authorized personnel. Secure the areas.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv.
Have the ACC unit inspected to determined why the ORP is low.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 13-October-2022


Comments
Please have violations brought into compliance for reinspection.