[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. pH is above 8.0.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
Repeat 12 ft. non-telescopic reach pole with shepherd's crook was not provided at the unguarded pool. The reach pole is provided; however, no crook is present.
Provide a 12 ft. non-telescopic reach pole in the pool area at all times.
3701-31-04(D)(6)(a)(1) / Combined chlorine shall not exceed 1.0 ppm.
Combined chlorine was greater than 1.0 ppm. Combined chlorine is 1.4 ppm.
Treat the pool so that the combined chlorine is less than 1 ppm.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 27-December-2023


Comments
Facility is clean at the time of inspection. The key to the pump room was not available at the time of inspection; ORP and flow values could not be obtained.