[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (D)(6)(a) / Pool free chlorine disinfectant residual is above 1 ppm.
Corrected During Inspection Pool free chlorine disinfectant residual was below 1 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Chlorine was hand fed into pool.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Follow-up

Inspection Date: 20-May-2014


The following violation(s) have been corrected since the last inspection.
3701-31-04 (C)(2)/pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8 at 8.0.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3)/Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
3701-31-04 ( D )(6)(a)/ORP reading is above 650 mv
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
Comments
A reinspection will be conducted to ensure proper level of chlorine in pool.