[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 14-July-2022


Comments
Chemicals within required range, no problems noted