3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Pool free chlorine disinfectant residual was below 1 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Correct By: 05-Sep-2023
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. Correct By: 05-Sep-2023
Facility Type: Spa
[?] Inspection Type: Follow-up
Inspection Date: 15-August-2023
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(6)(h)/Required meters and gauges maintained/functional Required meters and gauges were not maintained or were not functional while the pool is in operation. Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation. Correct By: 15-Aug-2023 |
3701-31-04(D)(6)(a)(1)/Combined chlorine shall not exceed 1.0 ppm. Combined chlorine was greater than 1.0 ppm. Treat the pool so that the combined chlorine is less than 1 ppm. Correct By: 15-Aug-2023 |
3701-31-04 (C)(3)/Total alkalinity is at or greater than 60 ppm Total alkalinity was less than 60 ppm. Raise the total alkalinity to at least 60 ppm. Correct By: 15-Aug-2023 |