3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation. Flow meter stuck.
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 13-August-2018