[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv. No ORP present. Alarm on.
Have the ACC unit inspected to determined why the ORP is low. Correct By: 26-Jul-2023
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. No flow observed.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. Correct By: 26-Jul-2023
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8. Observed at 8.0
Treat the pool water so that the pH is within the acceptable range. Correct By: 26-Jul-2023
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working. No dial tone.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities. Correct By: 26-Jul-2023


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 25-July-2023


Comments
ACC not working, ORP not present, no flow, high pH. All other parameters were within required ranges. Pool operator was on site and informed the inspector corrections were to be made same day. Follow up inspection to come.