[?] A summary of the violations found during the inspection are listed below.

No critical violations were documented at the time of inspection.

No violations were documented at the time of inspection.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Follow-up

Inspection Date: 27-June-2022


The following violation(s) have been corrected since the last inspection.
3701-31-04 ( D )(6)(a)/ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. Observed at 435mv.
Have the ACC unit inspected to determined why the ORP is low. Correct By: 01-Jul-2022
3701-31-04(D)(6)(a)(2)/Pool free chlorine disinfectant residual shall be above 1 ppm.
Pool free chlorine disinfectant residual was below 1 ppm. Observed at 0ppm
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Correct By: 27-Jun-2022
Comments
Follow up inspection after no chlorine was observed. Water quality is now within required parameters.