[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. ORP is 566. Please calibrate the controller.
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps. Bobber missing from flow meter.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.


Inspection Information


Facility Type: Special Use

[?] Inspection Type: Standard

Inspection Date: 31-July-2015


Comments
Chlorine and pH are within required ranges. Good Job.