[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day. Correct By: 31-Oct-2021
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test total alkalinity at least once/week. Correct By: 31-Oct-2021
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required flow meter gauge was not functional while the pool is in operation. The flow meter was stuck.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. Correct By: 31-Oct-2021


Inspection Information


Facility Type: Spa

[?] Inspection Type: Standard

Inspection Date: 30-September-2021


Comments
Ensure noted violations are corrected before next routine inspection. Otherwise, all other water parameters are within requirements. Good job!