3701-31-04 (D)(02) / Public swimming pool is continuously disinfected using a chemical feeding device connected to the circulation system
Critical Repeat The pool was not being continuously disinfected using a chemical feeding device connected to the circulation system. ACC is non-functioning and constantly alarming.
Repair or replace the disinfection system so that the pool is continuously being disinfected.
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv. ORP is 135 mv.
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Repeat Disinfection residuals were not tested daily at pool side and/or at the required intervals for pools/automatic chemical controllers/special features. Did not observe any records for March 26, 2024.
Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. If an ACC is in use the disinfectant residual must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the disinfectant residual must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Repeat Combined chlorine was not tested daily at pool side prior to use. No records for March 26, 2024.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Repeat pH was not tested daily at pool side and/or at required intervals for pools/automatic chemical controllers/special features. No records for March 26, 2024.
pH must be tested prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use pH must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the pH must be tested at 1 special feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm. Alkalinity is 50 ppm.
Raise the total alkalinity to at least 60 ppm.
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
Repeat The facility's test kit was not properly supplied with R-0871
Please provide R-0871 to ensure the pool chemistry can be tested at the required frequency.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 26-March-2024
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04(D)(6)(a)(2)/Pool free chlorine disinfectant residual shall be above 1 ppm. Pool free chlorine disinfectant residual was below 1 ppm. Free chlorine is 0.8 ppm. Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Correct By: 26-Mar-2024 |
Comments |
---|
Chlorine levels tested and are within required range. Facility has ordered R-0871 for testing kit. |