[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. The ORP was 207 mv.
Have the ACC unit inspected to determined why the ORP is low. Correct By: 31-Mar-2022
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working. Rosey stated, "she will have maintenance repair/replace phone immediately."
Ensure that the emergency device is functioning properly and rings to the emergency response authorities. Correct By: 31-Mar-2022


Inspection Information


Facility Type: Spa

[?] Inspection Type: Standard

Inspection Date: 28-February-2022


Comments
Ensure the noted finding is corrected before next routine inspection. Otherwise, all water parameters were within requirements at time of inspection. Furthermore, the reports were readily available for review. Good job!
Note: The chlorine is high; therefore, verify that auto controller is set properly for dispensing.