3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Disinfection residuals were not tested daily at pool side and/or at the required intervals for pools/automatic chemical controllers/special features. Due to the fact automatic controller was off readings required every 4 hours.
Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. If an ACC is in use the disinfectant residual must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the disinfectant residual must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (D)(6)(a) / Pool free chlorine disinfectant residual is above 1 ppm.
Corrected During Inspection Pool free chlorine disinfectant residual was below 1 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 03-June-2014
Comments |
---|
When I arrived there was no chlorine. Pool company arrived and corrected problem. Operator indicated an identical automatic controller would be installed within 4 hours. Reinspection will verify this. |