3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat No detectable level of chlorine was found in the spa.
3701-31-04 (B)(1)(d) / Circulation/Disinfection system shall operate properly.
Critical The chemical feeder for chlorine was removed with the ACC, and the chemical feeder for muriatic acid was no longer being used.
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection. The ACC was removed from the equipment room.
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
3701-31-04 (D)(7) / Public spa shall have a functional automatic chemical controller
Critical The automatic chemical controller was removed.
3701-31-04(D)(6)(a)(4) / Spa free chlorine disinfectant residual shall be above 2 ppm.
Critical Spa free chlorine disinfectant residual was below 2 ppm. No detectable level of chlorine was found in the spa.
Do not operate the spa until the chlorine disinfectant residual is at 2 ppm or above.
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. The ACC unit was removed.
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records. The facility was not maintaining accurate records of spa water testing. By the manager's admission the spa water would have no detectable chlorine residual in the morning, and then chlorine would be added to the spa to reach the minimum required disinfection residual. However, disinfection residual records were filled out with 2 ppm everyday, several times a day for weeks on end. This is inconsistent with the manager's account of spa operation. The facility is required to maintain accurate records of readings everyday.
All facility records must be maintained and available for review upon request.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Equipment was removed without approval.
All equipment must be maintained in accordance with the manufacturers specifications.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 29-April-2024
Comments |
---|
Facility had the automatic chemical controller uninstalled a couple years ago and removed the chlorine chemical feeder. The muriatic acid feeder was still hooked up, but was no longer in use. All chemicals were being added by hand to the pool every day. The facility will be required to replace any uninstalled equipment and provide an equipment replacement form to the state for approval. A warning sign was affixed to the door of the pool area informing the public of the conditions of the pool. The sign may only be removed after the necessary corrections have been made. |