3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Corrected During Inspection Pool free chlorine disinfectant residual was below 1 ppm. Observed at 0ppm, corrected onsite by PIC.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Correct By: 06-Jul-2023
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. Observed at 575mv.
Have the ACC unit inspected to determined why the ORP is low. Correct By: 06-Jul-2023
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat Corrected During Inspection pH was outside the range of 7.2 to 7.8. Observed at 7.0, corrected on site by PIC.
Treat the pool water so that the pH is within the acceptable range. Correct By: 06-Jul-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 05-July-2023
Comments |
---|
No chlorine present and low pH at time of inspection, both corrected on site by PIC. Low ORP reading was also recorded. Other water quality parameters were within the required ranges at this time. No other issues noted. |