3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat Pool free chlorine disinfectant residual was below 1 ppm. Observed at 0ppm
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Correct By: 02-Aug-2022
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv. Reading at 535 mv at time of inspection.
Have the ACC unit inspected to determined why the ORP is low. Correct By: 02-Aug-2022
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met. Minimum flow rate is 46gpm and the flow was observed at 30gpm
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. Correct By: 02-Aug-2022
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. Observed at 8.0
Treat the pool water so that the pH is within the acceptable range. Correct By: 02-Aug-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 26-July-2022
Comments |
---|
No chlorine observed, ORP reading low, pH too high, flow reading low. Operator present and corrected on site. Pool not to be in operation unless water quality parameters are met. Please ensure all noted findings are corrected prior to next inspection. |