[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(c) / Minimum disinfection residual provided as required
Critical Chlorine disinfectant residual was less than 1 ppm for the pool.No chlorine residual was detected.
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation. Correct By: 20-Aug-2014

3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation .Flow meter was stuck. Motor was running and there was flow but the amount could not be determined.
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation. Correct By: 20-Aug-2014
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8. The reading taken was at least an 8 if not higher.
Treat the pool water so that the pH is within the acceptable range. Correct By: 20-Aug-2014


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 19-August-2014


Comments
The three people in the pool were told the current level of chlorine was 0 but according to the records there was 3 ppm when the reading was taken 4 hours earlier at 10 am. The desk clerk who takes the readings was also told there was no chlorine in the pool and the recommendation is to close the pool until 1ppm free chlorine is detected. Also left my card with this information on the back with the clerk to give to the owner.