3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat There was no detectable level of chlorine in the pool at the time of inspection.
3701-31-04 (B)(1)(d) / Circulation/Disinfection system shall operate properly.
Critical The chemical feeders for chlorine had been removed and the feeder for muriatic acid was not being used.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat Pool free chlorine disinfectant residual was below 1 ppm. There was no detectable level of chlorine in the pool. According to the manager the when the water is tested in the morning there is no chlorine, and so chlorine is added by hand to the pool. The inspection was performed at 3:00 on a monday afternoon, and there was no chlorine present, since the pool was open bathers may have used the pool without any level of disinfection residual. This has occured during several previous inspections.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. The ACC unit was removed.
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Changes were made to the pool equipment room without plan approval.
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records. The facility was not maintaining accurate records of pool water testing. By the manager's admission the pool water would have no detectable chlorine residual in the morning, and then chlorine would be added to the pool to reach the minimum required disinfection residual. However, disinfection residual records were filled out with 2 ppm everyday, several times a day for weeks on end. This is inconsistent with the manager's account of pool operation. The facility is required to maintain accurate records of readings everyday.
All facility records must be maintained and available for review upon request.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Equipment was uninstalled from the pool equipment room without plan approval. The automatic chemical controller was removed, the chlorine feeder was removed, the acid feeder was no longer being used.
All equipment must be maintained in accordance with the manufacturers specifications.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 29-April-2024
Comments |
---|
Facility had the automatic chemical controller uninstalled a couple years ago and removed the chlorine chemical feeder. The muriatic acid feeder was still hooked up, but was no longer in use. All chemicals were being added by hand to the pool every day. The facility will be required to replace any uninstalled equipment and provide an equipment replacement form to the state for approval. A warning sign was affixed to the door of the pool area informing the public of the conditions of the pool. The sign may only be removed after the necessary corrections have been made. |