[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (D)(7)(a) / pH and ORP values for chlorine/bromine shall be continuously monitored.
Critical pH values were not continuously monitored.
Have the ACC unit serviced so that the pH values are continuously monitored

3701-31-04 (E)(2)(d) / First aid kit provided
Repeat First aid equipment was not provided.
Pleaes provide gloves in first aid kit.
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Repeat Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 05-July-2023


Comments
Chemical Controller was off at time of inspection, please ensure that a functional chemical controller is provided or that pool chemistry is tested every four hours. Please also include gloves in the first aid kit and provide a functional emergency phone. Flow gauge was stuck at bottom reading, please have it serviced. KJS