[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Repeat Disinfection residuals were not tested daily at pool side and/or at the required intervals for pools/automatic chemical controllers/special features. Due to the fact automatic controller was off readings required every 4 hours.
Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. If an ACC is in use the disinfectant residual must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the disinfectant residual must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Follow-up

Inspection Date: 05-June-2014


The following violation(s) have been corrected since the last inspection.
Comments
Thank you for replacing chlorine feeder with the same make and model.