[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Flow meter was stuck.
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation. Correct By: 23-Jul-2014
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Repeat Equipment/chemical/storage areas were not secured.
These storage areas must be kept inaccessible to everyone but authorized personnel. Secure the areas. Correct By: 23-Jul-2014


Inspection Information


Facility Type: Pool

[?] Inspection Type: Follow-up

Inspection Date: 23-July-2014


The following violation(s) have been corrected since the last inspection.
3701-31-04 (C)(2)/pH is within 7.2 to 7.8
ph is 8.0.
Treat the pool water so that the pH is within the acceptable range. Correct By: 23-Jul-2014
Comments
pH corrected. Pump room still must be locked and flow meter made functional.